The EL1262 digital input terminal acquires the fast binary control signals from the process level and transmits them, in an electrically isolated form, to the controller. The signals are oversampled with an adjustable, integer multiple (oversampling factor: n) of the bus cycle time (n microcycles per bus cycle). For each microcycle, the EtherCAT Terminal generates a process data block that is transferred collectively during the next bus cycle. The time base of the terminal can be synchronised precisely with other EtherCAT devices via distributed clocks. This procedure enables the temporal resolution of the digital input signals to be increased to n times the bus cycle time.
| Technical data | EL1262 | ES1262 |
|---|---|
| Number of inputs | 2 |
| Nominal voltage | 24 V DC (-15 %/+20 %) |
| “0“ signal voltage | -3…+5 V (EN 61131-2, type 1) |
| “1“ signal voltage | 11…30 V (IEC 61131-2, type 1) |
| Input current | typ. 3 mA |
| Input filter | typ. < 1 µs |
| Oversampling factor | n = integer multiple of the cycle time, 1…1,000, see documentation |
| Distributed clock precision | << 1 µs |
| Sampling rate | max. 1 Msample/s |
| Current consumption E-bus | typ. 70 mA |
| Electrical isolation | 500 Vrms (E-bus/field potential) |
| Bit width in the process image | n x 2 inputs + 64 bit CycleCounter/latch |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
Product announcement |
EL1262: available ES1262: estimated market release 1st quarter 2009 |