The EL2202 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. This terminal benefits from very small output delay and is therefore suitable for signals requiring particularly fast output. The EtherCAT Terminal supports distributed clocks, i.e. the output data can be monitored synchronously with other data from terminals with distributed clock support. The DC accuracy across the system is << 1 µs. The EtherCAT Terminal has a push-pull output that enables the output to be connected actively to 24 V, 0 V or high-resistance. The EL2202 contains two channels, whose signal state per channel is indicated via LEDs. Each output can be switched to high resistance.
| Technical data | EL2202 | ES2202 |
|---|---|
| Number of outputs | 2 |
| Rated load voltage | 24 V DC (-15 %/+20 %) |
| Load type | ohmic, inductive, lamp load |
| Distributed clocks | yes |
| Max. output current | 0.5 A (per channel) |
| Switching times | typ. TON: < 1 µs, typ. TOFF: < 1 µs |
| Output stage | push-pull |
| Current consumption E-bus | typ. 130 mA |
| Electrical isolation | 500 Vrms (E-bus/field potential) |
| Bit width in the process image | 2 outputs, 2 bit enable tri-state |
| Configuration | no address or configuration setting |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |