Digital Output
EL2502
 
2-channel pulse width output terminal 24 V DC EL2502
Signal LED1
Output 1
 +24 V
 0 V
 Signal LED2
 Output 2
Power contact 0 V
Power contact
+24 V
Power contact PE
Top view
Contact assembly
Connection
 PE

EL2502 | 2-channel pulse width output terminal 24 V DC

The EL2502 output terminal modulates the pulse width of a binary signal and outputs it electrically isolated from the E-bus. The mark/space ratio is prescribed by a 16 bit value from the automation unit. The output stage is protected against overload and short-circuit. The EtherCAT Terminal has two channels that indicate their signal state via LEDs. The LEDs are driven in time with the outputs, and show the mark/space ratio by their brightness.

Technical data EL2502 | ES2502
Number of outputs 2
Rated load voltage 24 V DC (-15 %/+20 %)
Load type ohmic, inductive
Max. output current 0.1 A (short-circuit-proof, 1 A driver component) per channel
Base frequency 1…20 kHz, 250 Hz default
Duty factor 0…100 % (TON > 750 ns, TOFF > 500 ns)
Resolution max. 10 bits
Current consumption E-bus 150 mA (see documentation)
Electrical isolation 500 Vrms (E-bus/field potential)
Current consumption power contacts typ. 10 mA + load
Bit width in the process image 2 x 16 bit PWM output
Configuration via TwinCAT System Manager
Weight approx. 50 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Product announcement
EL2502: available
ES2502: estimated market release 3rd quarter 2008