Analog Input
EL3204
 
4-channel input terminal PT100 (RTD) EL3204
Run LED1
Error LED1
Run LED3
Error LED3
+R1
-R3
-R1
+R3
 Run LED2
 Error LED2
 Run LED4
 Error LED4
 +R2
 -R2
+R4
 -R4
Power contact 0 V
Power contact
+24 V
Top view
Contact assembly
Connection
2-wire
+R
-R
+R
-R

EL3204 | 4-channel input terminal PT100 (RTD)

The EL3204 analog input terminal allows resistance sensors to be connected directly. The EtherCAT Terminal circuit can operate sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The EtherCAT Terminal’s standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors. Sensor malfunctions such as broken wires are indicated by error LEDs.

Technical data EL3204 | ES3204
Number of inputs 4
Power supply via the E-bus
Sensor types PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement 0…1/4 kΩ (e.g. for potentiometer)
Connection method 2-wire
Temperature range -250…+850 °C (PT sensors); -60…+250 °C (Ni sensors)
Resolution 0.1 °C per digit
Conversion time approx. 800 ms up to 2 ms, depending on configuration and filter setting, see documentation, default: approx. 85 ms
Measuring current typ. 0.5 mA
Measuring error < ±0.5 °C for PT sensors (further types see documentation)
Electrical isolation 500 Vrms (E-bus/signal voltage)
Current consumption E-bus 190 mA (see documentation)
Bit width in the process image 4 x 32 bit RTD input
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Product announcement
EL3204: available
ES3204: estimated market release 4th quarter 2008