The EL3314 analog input terminal allows four thermocouples to be connected directly. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3314 can also be used for mV measurement.
| Technical data | EL3314 |
|---|---|
| Number of inputs | 4 |
| Power supply | via the E-bus |
| Thermocouple sensor types | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
| Connection method | 2-wire |
| Temperature range | in the range defined in each case for the sensor (default setting: type K; -100…+1,370 °C) |
| Resolution | 0.1 °C per digit |
| Wiring fail indication | yes |
| Conversion time | approx. 2.5 s up to 20 ms, depending on configuration and filter setting, see documentation, default: approx. 250 ms |
| Measuring error | < ±0.3 % for type K (relative to full scale value), further types see documentation |
| Electrical isolation | 500 Vrms (E-bus/signal voltage) |
| Current consumption E-bus | 200 mA |
| Bit width in the process image | 4 x 32 bit TC input, 4 x 16 bit TC output |
| Configuration | no address setting, configuration via the controller |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |