Digital Input
KL1052
 
2-channel digital input terminal 24 V DC, switching to positive and negative potentials KL1052
Input 1
Power contacts
Input 2
+24 V
0 V
PE
Signal LED1
Signal LED2
4-wire
3-wire
2-wire
Top view
Contact assembly
Connection
positive negative

KL1052 | 2-channel digital input terminal 24 V DC, switching to positive and negative potentials

The KL1052 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. Sensors that switch to the positive potential or to 0 V (ground) can be connected to the KL1052 version. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes.

Technical data KL1052 | KS1052
Number of inputs 2
Nominal voltage 24 V DC (-15 %/+20 %)
“0“ signal voltage 7.6…17.4 V
“1“ signal voltage 0…7 V and 18…30 V
Input filter 3.0 ms
Input current typ. 3 mA
Current consumption K-bus typ. 8 mA
Electrical isolation 500 Vrms (K-bus/field potential)
Bit width in the process image 2 inputs
Configuration no address or configuration setting
Weight approx. 50 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Special terminals
KL1052-0010 96 V DC pos. and neg. switching, not in accordance with the IEC 1131 specifications: I high = 3 mA, I low = 0.5 mA