The KL1212 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The KL1212 generates a short-circuit protected 24 V DC supply voltage for sensors. The sensor outputs can be switched on or off by the controller. A short-circuit or an open lead in the sensor supply is detected, and the terminal status is relayed to the controller via the K-bus. The Bus Terminal contains two channels that indicate their signal state and errors by means of LEDs.
| Technical data | KL1212 | KS1212 | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Number of inputs | 2 | ||||||||||||||||
| Nominal voltage | 24 V DC (-15 %/+20 %) | ||||||||||||||||
| “0“ signal voltage | -3…+5 V | ||||||||||||||||
| “1“ signal voltage | 15…30 V | ||||||||||||||||
| Input filter | 3.0 ms | ||||||||||||||||
| Input current | typ. 5 mA | ||||||||||||||||
| Sensor supply max. | 0.5 A (short-circuit-proof) | ||||||||||||||||
| Current consumption K-bus | typ. 8 mA | ||||||||||||||||
| Electrical isolation | 500 Vrms (K-bus/field potential) | ||||||||||||||||
| Bit width in the process image | input/output: 4 inputs (2 error bits/2 signal bits); 2 outputs (2 sensor supply) | ||||||||||||||||
| Input/output bit assignments |
|
||||||||||||||||
| Configuration | no address or configuration setting | ||||||||||||||||
| Weight | 55 g | ||||||||||||||||
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | ||||||||||||||||
| Relative humidity | 95 %, no condensation | ||||||||||||||||
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | ||||||||||||||||
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | ||||||||||||||||
| Protect. class/installation pos. | IP 20/variable | ||||||||||||||||
| Pluggable wiring | for all KSxxxx Bus Terminals |
Product announcement |
KL1212: available KS1212: estimated market release 3rd quarter 2009 |