The up/down counter counts binary pulses, and transmits the counter state, in an electrically isolated form, to the higher-level automation device. Optionally the KL1512 Bus Terminal can be set up as an up or down counter (16 bit). The Bus Terminal contains two inputs that indicate their signal state by means of light emitting diodes. The KL1512 is particularly suitable for simple counting tasks, e.g. in connection with flow meters.
| Technical data | KL1512 | KS1512 |
|---|---|
| Number of inputs | 2 |
| Nominal voltage | 24 V DC (-15 %/+20 %) |
| “0“ signal voltage | -3…+5 V |
| “1“ signal voltage | 15…30 V |
| Counting frequency | max. 1 kHz |
| Counter depth | 16 bits |
| Input filter | 0.2 ms |
| Input current | typ. 5 mA |
| Electrical isolation | 500 Vrms (K-bus/field potential) |
| Bit width in the process image | input/output: 16 bit data, 8 bit control/status |
| Configuration | via the Bus Coupler or the controller |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
Product announcement |