Digital Output
KL2502
Output 1
Power contacts
Output 2
+24 V
0 V
PE
Signal LED1
Signal LED2
4-wire
3-wire
2-wire
Top view
Contact assembly
Connection
KL2502 | 2-channel pulse width output terminal 24 V DC
The KL2502 output terminal modulates the pulse width of a binary signal, and outputs it electrically isolated from the K-bus. The mark/space ratio is prescribed by a 16 bit value from the automation unit. The output stage is protected against overload and short-circuit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes. The LEDs are driven in time with the outputs and show the mark/space ratio by their brightness.
| Technical data |
KL2502 | KS2502 |
| Number of outputs |
2 |
| Rated load voltage |
24 V DC (-15 %/+20 %) |
| Load type |
ohmic, inductive |
| Max. output current |
0.1 A (short-circuit-proof, 1 A driver component) per channel |
| Base frequency |
1…20 kHz, 250 Hz default |
| Duty factor |
0…100 % (TON > 750 ns, TOFF > 500 ns) |
| Resolution |
max. 10 bits |
| Electrical isolation |
500 Vrms (K-bus/field potential) |
| Current consumption power contacts |
typ. 10 mA |
| Current consumption K-bus |
typ. 18 mA |
| Bit width in the process image |
48 inputs/outputs: 2 x 16 bit data, 2 x 8 bit control/status |
| Configuration |
no address setting, configuration via Bus Coupler or controller |
| Weight |
approx. 50 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all KSxxxx Bus Terminals |
| Special terminals |
|
| KL2502-0010 |
30 kHz stepper motor terminal |
| KL2502-0012 |
time-delayed setting of the outputs |
| KL2502-3020 |
5 V output, 30 kHz limit frequency |