The KL2641 output terminal has a relay with a single contact which can be used universally for switching devices requiring mains power. The relay can optionally be switched in manual or automatic mode. The switch for the manual operation always indicates the switch status of the relay. The operating mode can be set via a manual/automatic switch, is displayed via an LED and transferred to the process image as a status bit. In manual mode, the coil control is interrupted and the relay is operated via the manual switch. The manual operation can also be used without 24 V supply for switching the actuator. In automatic mode, the relay is operated via the controller.
| Technical data | KL2641 |
|---|---|
| Number of outputs | 1 make contact |
| Switching capacity max. | 5 kVA |
| Switching voltage max. | 440 V AC |
| Switching current max. | 16 A AC |
| Current consumption power contacts | 65 mA |
| Current consumption K-bus | typ. 5 mA |
| Contact material | AgSnO2 |
| Bit width in the process image | 2 inputs (status manual, automatic), 2 outputs |
| Operating cycles | 106 |
| Configuration | no address or configuration setting |
| Weight | 110 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |