The KL2692 Bus Terminal monitors a bit that is toggled by the controller during each cycle. If the toggle signal fails, the controller switches off two potential-free relay circuits in order to prevent damage to the machine. Failure of the toggle signal may be caused by the PLC cycle stopping, by a fault in the bus cable or connector, or by a fault in a bus device. The cycle monitoring time can be parameterised. The Bus Terminal has an enable input that enables the relay to be switched on if a correct toggle signal is detected.
| Technical data | KL2692 | KS2692 |
|---|---|
| Number of outputs | 2 potential-free relay outputs (normally-open contacts) |
| Number of inputs | 2 digital 24 V inputs |
| Rated load voltage | 230 V AC/30 V DC |
| Ohmic switching current | 5 A AC/DC |
| Inductive switching current | 2 A AC/DC |
| Minimum permitted load | 10 mA at 5 V DC |
| Electrical isolation | 500 Vrms (K-bus/field potential) |
| Current consumption K-bus | approx. 165 mA |
| Bit width in the process image | 2 x 8 bit data, 1 x 8 bit control/data |
| Operating cycles mech. (min.) | 2 x 107 |
| Operating cycles electr. (min.) | 1 x 105 (5 A/30 V DC) |
| Configuration | via the Bus Coupler or the controller |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |