Digital Output
KL2712
 
2-channel triac output terminal 12…230 V AC, 0.5 A KL2712
Output 1
Power contacts
Output 2
230 V
N
PE
Signal LED1
Signal LED2
Top view
Contact assembly
Connection

KL2712 | 2-channel triac output terminal 12…230 V AC, 0.5 A

The KL2712 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 0.5 A. The KL2712 terminal has two independent outputs. Its signal state is indicated by means of light emitting diodes.

Technical data KL2712 | KS2712
Number of outputs 2 x make contacts
Rated load voltage 12…230 V AC
Max. output current 0.01…0.5 A continous load per channel
Frequency range 47…63 Hz
Surge voltage protection > 275 V
Peak current 40 A (16 ms), 1.5 A (30 s)
Switch-on time 0.1 ms
Switch-off time T/2
Maximum residual voltage 1.5 V
Electrical isolation 500 Vrms (K-bus/field voltage), 3,750 V AC (1 min.)
Current consumption K-bus 10 mA
Bit width in the process image 2 outputs
Configuration no address or configuration setting
Weight approx. 55 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals