The KL2712 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 0.5 A. The KL2712 terminal has two independent outputs. Its signal state is indicated by means of light emitting diodes.
| Technical data | KL2712 | KS2712 |
|---|---|
| Number of outputs | 2 x make contacts |
| Rated load voltage | 12…230 V AC |
| Max. output current | 0.01…0.5 A continous load per channel |
| Frequency range | 47…63 Hz |
| Surge voltage protection | > 275 V |
| Peak current | 40 A (16 ms), 1.5 A (30 s) |
| Switch-on time | 0.1 ms |
| Switch-off time | T/2 |
| Maximum residual voltage | 1.5 V |
| Electrical isolation | 500 Vrms (K-bus/field voltage), 3,750 V AC (1 min.) |
| Current consumption K-bus | 10 mA |
| Bit width in the process image | 2 outputs |
| Configuration | no address or configuration setting |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |