Analog Input
KL3064
 
4-channel analog input terminal 0…10 V KL3064
+ Input 1
+ Input 3
Ground
Shield
+ Input 2
+ Input 4
Ground
Shield
Run LED1
Run LED2
Run LED3
Run LED4
Top view
Contact assembly
Connection

KL3064 | 4-channel analog input terminal 0…10 V

The KL3064 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitised to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of a Bus Terminal have a common ground potential. The KL3064 combines four channels in one housing. The run LEDs give an indication of the data exchange with the Bus Coupler.

Technical data KL3064 | KS3064
Number of inputs 4 (single-ended)
Power supply via the K-bus
Signal voltage 0…10 V
Internal resistance > 130 kΩ
Resolution 12 bits
Conversion time ~ 4 ms
Measuring error < ±0.3 % (relative to full scale value)
Electrical isolation 500 Vrms (K-bus/signal voltage)
Current consumption K-bus typ. 85 mA
Bit width in the process image input: 4 x 16 bit data (4 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 80 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Special terminals
KL3064-0010 Siemens S5 format
KL3064-0050 Siemens S7 format