The KL6051 serial interface terminal makes it possible to exchange data between different fieldbus systems. Full duplex data exchange is possible, independently of the higher-level fieldbus. Under the terminal’s default setting, 32 inputs and 32 outputs are transferred between the fieldbus systems. The time to exchange the data is about 5 ms for 32 bits of I/O. The exchange of data with the Bus Coupler is indicated by the run LED. The TxD and RxD LEDs indicate the state of the signal transmission.
| Technical data | KL6051 | KS6051 |
|---|---|
| Data transfer channels | TxD and RxD, full duplex |
| Data transfer rates | 62,500 baud, 8 data bits, no parity, one stop bit |
| Bit transfer | via 2 pairs of twisted wires with differential signals |
| Line impedance | 120 Ω |
| Cable length | approx. 1,000 m twisted pair |
| Power supply | via the K-bus |
| Current consumption K-bus | typ. 65 mA |
| Electrical isolation | 500 Vrms (K-bus/signal voltage) |
| Bit width in the process image | input/output: 4 x 8 bit user data, 1 x 8 bit control/status (up to 5 x 8 bit user data are possible) |
| Configuration | no address or configuration setting |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |