2-channel digital input terminal 24 V DC KL1002
Signal LED1
Signal LED2
Power contact
+24 V
Power contact 0 V
Power contact PE
Input 1
Input 2
+24 V
0 V
PE
Top view 
Contact assembly 
extended temperature range
extended shock and vibration range

KL1002 | 2-channel digital input terminal 24 V DC

The KL1002 digital input terminal acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes.

Technical data KL1002 | KS1002
Connection technology 4-wire
Specification EN 61131-2, type 1/3
Number of inputs 2
Nominal voltage 24 V DC (-15 %/+20 %)
“0“ signal voltage -3…+5 V
“1“ signal voltage 15…30 V
Input filter typ. 3.0 ms
Input current typ. 5 mA
Current consumption K-bus typ. 3 mA
Electrical isolation 500 V (K-bus/field potential)
Bit width in the process image 2 inputs
Configuration no address or configuration setting
Weight approx. 50 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals CE, UL, Ex, GL