The digital KL1362 input terminal analyses the input signals of break-in sensors with the aid of a current loop. Alarm contacts with a fixed resistance ratio can be monitored safely. In the process image, the state of the sensor is indicated by one bit each. A further bit reports short-circuits or line interruptions. Red or green LEDs indicate the state of the two input bits.
| Technical data | KL1362 | KS1362 |
|---|---|
| Number of inputs | 2 |
| Nominal voltage | 24 V (-15 %/+20 %) |
| “0“ signal current | ≤ 1 mA |
| “1“ signal current | ≥ 1 mA |
| Operating voltage | 5.1 V |
| Line interruption | < 0.1 mA |
| Short circuit | > 3 mA |
| Cable resistance | ≤ 200 Ω |
| Input filter | 3.0 ms |
| Current consumption K-bus | typ. 5 mA |
| Electrical isolation | 500 Vrms (K-bus/field potential) |
| Bit width in the process image | 4 inputs |
| Configuration | no address or configuration setting |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
Product announcement |