The KL2184 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. The KL2184 version has four 0 V (ground) switching outputs and generates load currents with outputs that are resistant to overload and short-circuit. The Bus Terminal contains four channels that indicate their signal state by means of light emitting diodes.
| Technical data | KL2184 | KS2184 |
|---|---|
| Number of outputs | 4 |
| Rated load voltage | 24 V DC (-15 %/+20 %) |
| Load type | ohmic, inductive, lamp load |
| Max. output current | 0.5 A (short-circuit-proof) per channel |
| Electrical isolation | 500 Vrms (K-bus/field potential) |
| Current consumption power contacts | 30 mA |
| Current consumption K-bus | 9 mA |
| Bit width in the process image | 4 outputs |
| Configuration | no address or configuration setting |
| Weight | approx. 70 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |