The KL2652 output terminal has two relays, each featuring a change-over contact. The relay contact can be used universally for switching devices requiring mains power up to 230 V AC or 300 V DC. The KL2652 Bus Terminal is equipped with potential-free contacts. The signal state of the Bus Terminal is indicated via LEDs.
| Technical data | KL2652 | KS2652 |
|---|---|
| Number of outputs | 2 x change-over |
| Switching voltage max. | 250 V AC, 300 V DC |
| Switching current max. | 1 A AC/1 A DC at 40 V DC; 0.15 A at 300 V DC (UL: max. 230 V AC, 1 A) |
| Minimum permitted load | 100 mA (12 V DC) |
| Electrical isolation | 1.5 kVrms (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III |
| Current consumption K-bus | 90 mA |
| Bit width in the process image | 2 outputs |
| Switching frequency max. | 6/min. (at rated load) |
| Operating cycles mech. (min.) | 5 x 106 |
| Operating cycles electr. (min.) | 1 x 106 (1 A AC/250 V AC) |
| Configuration | no address or configuration setting |
| Weight | approx. 55 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
Product announcement |
KL2652: available KS2652: estimated market release 3rd quarter 2009 |