Analog Input
KL3228
 
8-channel input terminal PT1000, Ni1000 (RTD) KL3228
+ R6
+ R8
+ R1
+ R2
+ R2
+ R4
Top view
Contact assembly
Connection
+ R5
+ R7
Error LED1
Error LED5
Error LED3
Error LED7
Error LED2
Error LED4
Error LED6
Error LED8
0 V
0 V
Power contact 0 V
Power contact
+24 V
+R
+R
+R
+R

KL3228 | 8-channel input terminal PT1000, Ni1000 (RTD)

The KL3228 analog input terminal enables connection of eight resistance sensors. The Bus Terminal’s circuitry can handle sensors using the 1-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminal’s standard settings are: resolution 0.1 °C within the temperature range of Ni1000 sensors. The error LEDs indicate sensor faults (e.g. a broken wire).

Technical data KL3228 | KS3228
Number of inputs 8
Power supply via the K-bus
Sensor types PT1000, Ni1000, PTC
Connection method 1-wire
Temperature range -50…+150 °C (PT sensors); -50…+150 °C (Ni sensors)
Resolution 0.1 °C per digit
Conversion time ~ 750 ms
Measuring current ~ 0.5 mA typ.
Measuring error ~ ±1 °C, depending on wiring
Electrical isolation 500 Vrms (K-bus/signal voltage)
Current consumption K-bus typ. 85 mA
Bit width in the process image input: 8 x 16 bit data (8 x 8 bit control/status optional)
Configuration no address setting, configuration via Bus Coupler or controller
Weight 75 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Product announcement
estimated market release 1st quarter 2009