Analog Input
KL3351
 
1-channel resistor bridge terminal (strain gauge) KL3351
+UD
-UD
-Uv = 0 V
Shield
+UREF
-UREF
+Uv = 5 V
Shield
Run LED1
Run LED2
Error LED1
Error LED2
Top view
Contact assembly
Connection
+Uv
+UREF
-UD
+UD
-UREF
-Uv
The supply voltage Uv can be drawn from the terminal or can be supplied from an external source. The terminal supplies 5 V. The maximum input voltage UREF is limited to 10 V.

KL3351 | 1-channel resistor bridge terminal (strain gauge)

The KL3351 analog input terminal permits direct connection of a resistor bridge. The bridge voltage, UD, and the supply voltage, UREF, to the bridge are digitised with a 16 bit resolution, and are transmitted along an electrically isolated channel to the supervising automation system. The input channels are available in the form of two 16 bit values for further processing. The resulting measurement can be calculated from the formula: measurement = UD/UREF. Precise acquisition of the supply voltage along with the bridge voltage compensates for long-term and temperature drift.

Technical data KL3351 | KS3351
Number of inputs 2, for one resistor bridge
Power supply via the K-bus
Signal voltage UD -16…+16 mV, configurable
Signal voltage UREF -10…+10 V, configurable
Internal resistance > 200 kΩ (UREF), > 1 MΩ (UD)
Power supply UV 5 V, max. 20 mA
Resolution 16 bits
Conversion time < 250 ms, configurable
Filter 50 Hz, configurable
Measuring error < ±0.1 % (relative to full scale value)
Current consumption K-bus typ. 65 mA
Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control/status optional)
Weight 70 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Special terminals
KL3351-0001 with faster measurement time > 10 ms