Analog Output
KL4132
 
2-channel analog output terminal -10…+10 V KL4132
+ Output 1
Ground
Shield
+ Output 2
Ground
Shield
Run LED1
Run LED2
Top view
Contact assembly
Connection

KL4132 | 2-channel analog output terminal -10…+10 V

The KL4132 analog output terminal generates signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels of a Bus Terminal have a common ground potential. The two run LEDs give an indication of the data exchange with the Bus Coupler.

Technical data KL4132 | KS4132
Number of outputs 2
Power supply via the K-bus
Signal voltage -10…+10 V
Load > 5 kΩ
Measuring error < ±0.1 % (relative to full scale value)
Resolution 16 bits
Conversion time ~ 1.5 ms
Electrical isolation 500 Vrms (K-bus/signal voltage)
Current consumption K-bus 75 mA
Bit width in the process image output: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Special terminals
KL4132-0010 Siemens S5 format
KL4132-0050 Siemens S7 format