Analog Output
KL4132
+ Output 1
Ground
Shield
+ Output 2
Ground
Shield
Run LED1
Run LED2
Top view
Contact assembly
Connection
KL4132 | 2-channel analog output terminal -10…+10 V
The KL4132 analog output terminal generates signals in the range from -10 to +10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels of a Bus Terminal have a common ground potential. The two run LEDs give an indication of the data exchange with the Bus Coupler.
| Technical data |
KL4132 | KS4132 |
| Number of outputs |
2 |
| Power supply |
via the K-bus |
| Signal voltage |
-10…+10 V |
| Load |
> 5 kΩ |
| Measuring error |
< ±0.1 % (relative to full scale value) |
| Resolution |
16 bits |
| Conversion time |
~ 1.5 ms |
| Electrical isolation |
500 Vrms (K-bus/signal voltage) |
| Current consumption K-bus |
75 mA |
| Bit width in the process image |
output: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Configuration |
no address or configuration setting |
| Weight |
approx. 85 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all KSxxxx Bus Terminals |
| Special terminals |
|
| KL4132-0010 |
Siemens S5 format |
| KL4132-0050 |
Siemens S7 format |