Special Function
KL6771
 
MP-Bus master terminal KL6771
MP-Bus
Top view
Contact assembly
Run
Send
MP-Bus error
Receive
Enable
+ 24 V
0 V
MP-Bus
slave
Power contact 0 V
Power contact
+24 V
5
2
1

KL6771 | MP-Bus master terminal

The MP-Bus master terminal enables direct connection of MP-Bus slave devices. The MP-Bus was developed by Belimo for connecting valves, throttle valves, air valves and fire dampers for window ventilation systems. Up to sixteen field devices, eight drives and eight sensors can be connected to the KL6771. Process data exchange is fieldbus-independent. The Bus Terminal is configured and commissioned via TwinCAT function blocks. Status LEDs directly indicate the bus status. Several KL6771 terminals can be connected to the same Bus Coupler or Bus Terminal Controller.

Technical data KL6771 | KS6771
Data transfer channels 1
MP-Bus devices max. 16 (8 drives/8 sensors)
Data transfer rates 1,200 baud
Current consumption K-bus approx. 55 mA
Short-circuit-proof yes
Electrical isolation 500 Vrms (K-bus/MP-Bus)
Bit width in the process image input/output: 12 bytes
Configuration TwinCAT (function blocks)
Input voltage 24 V DC (-15 %/+20 %)
Weight approx. 80 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Product announcement
KL6771: available
KS6771: estimated market release 3rd quarter 2009