The analog KM4602 output terminal has two potential-free analog 0 to 10 V outputs. Both are connected internally to common ground. For each channel a switch enables selection between automatic or manual mode. In automatic mode an analog value is issued depending on the process data. With the manual switch settings the value set via the potentiometer is applied to the output. For manual mode a 24 V supply is required for the Bus Coupler. The switch state can be read by the controller.
| Technical data | KM4602 |
|---|---|
| Power supply | via the K-bus |
| Signal voltage | 0…10 V |
| Load | > 5 kΩ (short-circuit-proof) |
| Measuring error | ±0.5 LSB linearity error, ±0.5 LSB offset error, ±0.1 % (relative to full scale value) |
| Resolution | 12 bits |
| Conversion time | ~ 1.5 ms |
| Electrical isolation | 500 Vrms (K-bus/signal voltage) |
| Current consumption K-bus | 75 mA |
| Configuration | no address or configuration setting |
| Weight | approx. 85 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
Product announcement |
estimated market release 3rd quarter 2008 |