Analog Output
KM4602
 
2-channel analog output terminal 0…10 V, manual/automatic operation KM4602
Top view
Control element
output voltage
manual operation (Output 1)
Control element
output voltage
manual operation (Output 2)
Manual/automatic
operation (Output 1
Manual/automatic
operation (Output 2)
Output 1
Output 2

KM4602 | 2-channel analog output terminal 0…10 V, manual/automatic operation

The analog KM4602 output terminal has two potential-free analog 0 to 10 V outputs. Both are connected internally to common ground. For each channel a switch enables selection between automatic or manual mode. In automatic mode an analog value is issued depending on the process data. With the manual switch settings the value set via the potentiometer is applied to the output. For manual mode a 24 V supply is required for the Bus Coupler. The switch state can be read by the controller.

Technical data KM4602
Power supply via the K-bus
Signal voltage 0…10 V
Load > 5 kΩ (short-circuit-proof)
Measuring error ±0.5 LSB linearity error, ±0.5 LSB offset error, ±0.1 % (relative to full scale value)
Resolution 12 bits
Conversion time ~ 1.5 ms
Electrical isolation 500 Vrms (K-bus/signal voltage)
Current consumption K-bus 75 mA
Configuration no address or configuration setting
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Product announcement
estimated market release 3rd quarter 2008