The EL6631 PROFINET IO controller (master) terminal supports the complete real-time function (RT) as well as extensive diagnostic possibilities. All services in accordance with Conformance Class B are supported. Up to 15 PROFINET IO devices can be projected on the EL6631.
The EL6631-0010 PROFINET IO device (slave) terminal enables simple exchange of data between EtherCAT and PROFINET IO. It is a device in the EtherCAT strand, which can consist of up to 65,535 devices. The EL6631-0010 has a 3-port switch. Two ports are fed to the outside on RJ 45 sockets. This allows the I/O stations to be structured as a line topology, as a result of which the wiring is simplified. The maximum distance between two devices is 100 m.
Protocols such as LLDP or SNMP can be used for network diagnosis.
| Technical data | EL6631 | EL6631-0010 |
|---|---|---|
| Technology | PROFINET IO | |
| Number of ports/channels | 2 | |
| Ethernet interface | 100BASE-TX Ethernet with 2 x RJ 45 | |
| Fieldbus | PROFINET IO controller | PROFINET IO device |
| Cable length | up to 100 m twisted pair | |
| Hardware diagnosis | status LEDs | |
| Power supply | via the E-bus | |
| Electrical isolation | 500 V (E-bus/Ethernet) | |
| Protocol | RT | |
| Configuration | via EtherCAT master | |
| Current consumption E-bus | typ. 400 mA | |
| Special features | LLDP, SNMP, Conformance Class B, max. 5 IRT devices, max. 15 RT devices, min. 1 ms RT cycle |
|
| Weight | approx. 75 g | |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Relative humidity | 95 %, no condensation | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 20/see documentation | |
![]() |
![]() |
![]() |
| System | |
|---|---|
| PROFINET | For further PROFINET products please see the system overview. |
![]() |
![]() |