System Terminals
EL9560
 
Power supply terminal 24 V DC/24 V DC, 0.5 A EL9560
Power LED
+24 V
Access to 24 V
Access to 0 V
PE
 Power LED
 0 V
 PE
 Power
 contact
 Power
 contact
 Power
 contact
Top view
Contact assembly

EL9560 | Power supply terminal 24 V DC/24 V DC, 0.5 A

The EL9560 power supply unit terminal generates an electrically isolated output voltage from the 24 V DC input voltage. The output voltage can be accessed at the terminal. The following EtherCAT Terminals are also supplied with this voltage via the power contacts. The power LEDs indicate the operating state of the terminal. The input voltage and the output voltage of 500 V are electrically isolated.

Technical data EL9560 | ES9560
Short-circuit-proof yes, automatic restart
Input voltage 24 V DC (-15 %/+20 %)
Output voltage 24 V DC (-15 %/+5 %)
Output current ≤ 0.5 A
Short circuit current approx. 0.6 A
Efficiency approx. 85 %
Current consumption E-bus 90 mA (see documentation)
Insulation voltage 1,500 V AC constant load field side/E-bus
Insulation voltage input/output 500 V AC permanent load
Weight approx. 65 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all ESxxxx terminals
Product announcement