The EL9560 power supply unit terminal generates an electrically isolated output voltage from the 24 V DC input voltage. The output voltage can be accessed at the terminal. The following EtherCAT Terminals are also supplied with this voltage via the power contacts. The power LEDs indicate the operating state of the terminal. The input voltage and the output voltage of 500 V are electrically isolated.
| Technical data | EL9560 | ES9560 |
|---|---|
| Short-circuit-proof | yes, automatic restart |
| Input voltage | 24 V DC (-15 %/+20 %) |
| Output voltage | 24 V DC (-15 %/+5 %) |
| Output current | ≤ 0.5 A |
| Short circuit current | approx. 0.6 A |
| Efficiency | approx. 85 % |
| Current consumption E-bus | 90 mA (see documentation) |
| Insulation voltage | 1,500 V AC constant load field side/E-bus |
| Insulation voltage input/output | 500 V AC permanent load |
| Weight | approx. 65 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |
Product announcement |