The EP6224 IO-Link module enables connection of up to four IO-Link devices, e.g. actuators, sensors or combinations of both. A point-to-point connection is used between the terminal and the device. The terminal is parameterised via the EtherCAT master. IO-Link is designed as an intelligent link between the fieldbus level and the sensor, wherein parameterisation information can be exchanged bidirectionally via the IO-Link connection. The parameterisation of the IO-Link devices with service data can be done from TwinCAT via ADS.
In the standard setting, the EP6224 functions as a 4-channel input terminal, 24 V DC, which communicates with connected IO-Link devices, parameterises them and, if necessary, changes their operating mode.
| Technical data | EP6224-0002 | EP6224-2022 |
|---|---|---|
| Data transfer rates | 4.8 kbaud, 38.4 kbaud and 230.4 kbaud | |
| Connection method | screw type M12 | |
| IO-Link interfaces | 4 | |
| Nominal voltage | 24 V DC (-15 %/+20 %) | |
| Distributed clocks | – | |
| Cable length | max. 20 m | |
| Sensor supply | +5 V DC, 20 mA each | |
| Current consumption from US (without sensor current) | typ. 130 mA + load | |
| Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin | |
| Electrical isolation | 500 V | |
| Supply current for devices | < 200 mA per device (method 1) | |
| Weight | approx. 165 g | approx. 250 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable | |
![]() |
![]() |
![]() |
Product announcement |