Communication
EP6224-xxx2
 
EP6224-0002 | IO-Link master
EP6224-0002
Connector
assignment
I/O
connection
M12 I/O
connection sockets
Signal status display
Labelling areas
Power supply
status display:
Box supply (US)
Auxiliary voltage (UP)
1 | 24 V DC
2 | n. c.
3 | GND
4 | C/Qx
5 | n. c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
Power supply feed
Power supply down-
stream connection
EtherCAT
signal input
EtherCAT
signal output
EP6224-2022 | IO-Link master
EP6224-2022
Connector
assignment
I/O
connection
M12 I/O
connection sockets
Labelling areas
1 | 24 V DC
2 | n. c.
3 | GND
4 | C/Qx
5 | n. c.
1 | Tx+
2 | Rx+
3 | Rx-
4 | Tx-
1 | + 24 V DC Us
2 | + 24 V DC UP
3 | GNDs
4 | GNDP
Power supply feed
Power supply down-
stream connection
EtherCAT
signal input
EtherCAT
signal output

EP6224-xxx2 | IO-Link master

In the standard setting, the EP6224 functions as a 4-channel input terminal, 24 V DC, which communicates with connected IO-Link devices, parameterises them and, if necessary, changes their operating mode.

Technical data EP6224-0002 EP6224-2022
Data transfer rates 4.8 kbaud, 38.4 kbaud and 230.4 kbaud
Connection method screw type M12
IO-Link interfaces 4
Nominal voltage 24 V DC (-15 %/+20 %)
Distributed clocks
Cable length max. 20 m
Sensor supply +5 V DC, 20 mA each
Current consumption from US (without sensor current) typ. 130 mA + load
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Electrical isolation 500 V
Supply current for devices < 200 mA per device (method 1)
Weight approx. 165 g approx. 250 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Product announcement
EP6224-2022: available
EP6224-0002: estimated market release on request