IE6002 | 1-channel serial interface, RS232

The IE6002 serial interface module allows the connection of devices with an RS232 interface, which operates in conformity with the CCITT V.28/DIN 66 259-1 standards. The module transmits the data in a fully transparent manner to the higher-level automation device. The data is transferred via the fieldbus using a simple handshake protocol. This does not have any effect on the protocol of the serial interface. The active serial communication channel functions independently of the higher-level bus system in full duplex mode at up to 115,200 baud, while a 128 byte receive buffer and a 16 byte send buffer are available. The RS232 interface guarantees high immunity to interference through electrically isolated signals.

Technical data IE6002
Data transfer channels 2 (1/1), TxD and RxD
Data transfer rates 1,200…115,200 baud, 9,600 baud (8 bits, no parity, 1 stop bit) is preset
RS232 connection M12, screw type
Nominal voltage 24 V DC (-15 %/+20 %)
Bit distortion < 3 %
Cable length max. 15 m
“0“ signal voltage -18…+3 V
“1“ signal voltage 3…18 V
Data buffer 128 bytes receive buffer, 16 bytes transmit buffer
Power supply connection feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Current consumption from US (without sensor current) 40 mA
Bit width in the process image input/output: 3 x 8 bit user data, 1 x 8 bit control/status (up to 5 x 8 bit user data are possible)
Electrical isolation RS232/control voltage: 500 V, to the fieldbus: yes, via IP-Link
Operating/storage temperature 0…+55 °C/-25…+85 °C
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 65/66/67 (conforms to EN 60529)/variable
Approvals CE, UL