BK5150 | CANopen “Compact” Bus Coupler
The “Compact” Bus Coupler BK5150 for CANopen extends the Beckhoff Bus Terminal system by a cost-optimised version in a compact housing. Up to 64 Bus Terminals are supported; with the terminal bus extension, up to 255 Bus Terminals can be connected. The CANopen Bus Coupler offers automatic baud rate detection up to 1 Mbaud and two address selection switches for address assignment. A 5-pin connector for the fieldbus connection is included in the scope of supply. Optionally, the ZS1052-3000 connector with integrated terminating resistor can be connected.
| System data |
CANopen | BK5150 |
| Number of I/O stations |
64 (255 with K-bus extension) |
| Number of I/O points |
depends on the structure |
| Data transfer medium |
screened, twisted copper cable, 2 x signal, 1 x ground (recommended) |
| Max. cable length |
| 5,000 m |
2,500 m |
1,000 m |
500 m |
250 m |
100 m |
40 m |
|
| Data transfer rates |
| 10 kbaud |
20 kbaud |
50 kbaud |
100/125 kbaud |
250 kbaud |
500 kbaud |
1,000 kbaud |
|
| PDO modes |
synchron, cyclic, event driven, polling |
 |
 |
| Technical data |
BK5150 |
| Number of Bus Terminals |
64 (255 with K-bus extension) |
| Max. number of bytes fieldbus |
16 Tx/Rx PDOs |
| Number of PDOs (CANopen) |
16 Tx/Rx PDOs |
| Additional CANopen features |
life, node guarding, emergency object, variable mapping, store/restore |
| Data transfer rates |
automatic detection up to 1 Mbaud |
| Bus interface |
open style connector, 5-pin |
| Power supply |
24 V DC (-15 %/+20 %) |
| Serial interface |
configuration interface |
| Diagnostics LED |
2 x power supply, 2 x K-bus, 2 x fieldbus |
| Current supply K-bus |
1750 mA |
| Weight |
approx. 100 g |
| Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Approvals |
CE, UL, Ex |
 |
 |
| Accessories |
|
| KS2000 |
configuration software for extended parameterisation |
| Cordsets |
cordsets and connectors |
| FC5101 | FC5102 |
CANopen PCI fieldbus cards |
 |
 |
| Related products |
|
| BK5110 |
CANopen Coupler for up to 64 digital Bus Terminals |
| BK5120 |
CANopen “Economy plus” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension) |
| BK5151 |
CANopen “Compact” Bus Coupler for up to 64 Bus Terminals (255 with K-bus extension) |
| LC5100 |
CANopen “Low Cost“ Bus Coupler version for up to 64 digital Bus Terminals (255 with K-bus extension) |
| BC5150 |
CANopen “Compact” Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension) |
| BX5100 |
CANopen Bus Terminal Controller for up to 64 Bus Terminals (255 with K-bus extension) |
| CX8051 |
CANopen Embedded PC, slave |
 |
 |