The EJ3202 EtherCAT plug-in module allows resistance sensors to be connected directly. The module's circuitry can operate 2- and 3-wire sensors. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The EJ3202’s standard settings are: resolution 0.1°C in the temperature range of Pt100 sensors in 3-wire connection. The signal state is indicated by light emitting diodes. Sensor malfunctions such as broken wires are indicated by error LEDs.
Product status:
regular delivery
Product information
| Technical data | EJ3202 |
|---|---|
| Connection method | 2- or 3-wire (default: 2-wire) |
| Number of inputs | 2 |
| Measuring range | -200…+850°C (Pt sensors); -60…+250°C (Ni sensors) |
| Power supply | via the E-bus |
| Technology | temperature measurement (RTD) |
| Distributed clocks | – |
| Input filter limit frequency | typ. 1 kHz |
| Sensor types | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation) |
| Conversion time | approx. 85 ms default setting, 2…800 ms configurable |
| Resolution | 0.1°C per digit |
| Measurement error/uncertainty | < ±0.5°C for Pt sensors |
| Electrical isolation | 500 V (E-bus/field potential) |
| Current consumption E-bus | typ. 165 mA |
| Special features | integrated digital filter, limit value monitoring, variable connection technology |
| Weight | approx. 30 g |
| Storage temperature | -40…+85°C |
| Operating temperature | -25…+60°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. | IP20/see documentation |
| Approvals/markings | CE, UL |
| Housing data | EJ_12_16pin_Code16 |
|---|---|
| Design form | EtherCAT I/O plug-in module |
| Material | polycarbonate |
| Installation | on signal distribution board |
| Mechanical coding | EJ plug-in module: signal-specific coding pins on the housing, signal distribution board: holes in the printed circuit board |
| Position of the coding pins | 1, 6 |
| Locking | latching lug in circuit board cut-out |
| Connection method | field wiring: application-specific wiring level on the signal distribution board,
EJ plug-in module: 2 x 20-pin socket strip |
| Dimensions (W x H x D) | 12 mm x 66 mm x 55 mm |