The EL1024 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The EtherCAT Terminal has four channels that indicate their signal state via light emitting diodes.
Special features:
- input specification type 2
 - no bouncing due to mechanical switches thanks to 3 ms input filter
 - direct connection of four 2-wire sensors via additional +24 V connection points
 
Product status:
regular delivery
Product information
| Technical data | EL1024 | 
|---|---|
| Connection technology | 2-wire | 
| Specification | EN 61131-2, type 2 | 
| Number of inputs | 4 | 
| Nominal voltage | 24 V DC (-15%/+20%) | 
| “0” signal voltage | -3…+5 V (EN 61131-2, type 2) | 
| “1” signal voltage | 11…30 V (EN 61131-2, type 2) | 
| Input current | typ. 6 mA (EN 61131-2, type 2) | 
| Input filter | typ. 3.0 ms | 
| Distributed clocks | – | 
| Current consumption power contacts | typ. 30 mA + load | 
| Current consumption E-bus | typ. 90 mA | 
| Electrical isolation | 500 V (E-bus/field potential) | 
| Configuration | no address or configuration setting | 
| Special features | type 2 | 
| Weight | approx. 50 g | 
| Operating temperature | 0…55°C | 
| Storage temperature | -25…+85°C | 
| Relative humidity | 95%, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP20/variable | 
| Pluggable wiring | for all ESxxxx terminals | 
| Approvals/markings | CE, CCC, UL, ATEX, IECEx | 
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc  | 
| Housing data | EL-12-8pin | ES-12-8pin | 
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level | 
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm²,  st*: 0.08…2.5 mm², f*: 0.14…1.5 mm²  | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm²  | 
| Connection cross-section AWG | s*: AWG28…14,  st*: AWG28…14, f*: AWG26…16  | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16  | 
| Stripping length | 8…9 mm | 9…10 mm | 
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL1024 | EtherCAT Terminal, 4-channel digital input, 24 V DC, 3 ms, type 2 | 
| ES1024 | EtherCAT Terminal, 4-channel digital input, 24 V DC, 3 ms, type 2, plug-in wiring level | 