The EL2652 output terminal has two relays each with a changeover contact, which can be used universally for the switching of mains voltage consumers of 230 V AC or 300 V DC. The EL2652 features potential-free contacts. The signal state of the EtherCAT Terminal is indicated by light emitting diodes.
Special features:
- relay output
 - 2x changeover contacts
 - Reverse switching is possible.
 - connection of different load types (ohmic, inductive, lamp load)
 - potential-free
 - no power contacts
 
Product status:
regular delivery
Product information
| Technical data | EL2652 | 
|---|---|
| Connection technology | relay output | 
| Number of outputs | 2 x change-over | 
| Switching voltage max. | 250 V AC, 300 V DC | 
| Nominal voltage | 230 V AC (max. switching voltage 250 V AC/300 V DC) | 
| Load type | ohmic, inductive, lamp load | 
| Distributed clocks | – | 
| Ohmic switching current | 1 A AC/DC (at 40 V DC), 0.15 A DC (at 300 V DC), for UL: 1 A, max. 230 V AC | 
| Minimum permitted load | 100 mA at 12 V | 
| Current consumption E-bus | 180 mA | 
| Current consumption power contacts | – | 
| Max. switching frequency | 6/min. (at rated load) | 
| Operating cycles mech. (min.) | 5 x 106 | 
| Operating cycles electr. (min.) | 1 x 106 (1 A/250 V AC ohmic load) | 
| Electrical isolation | 1.5 kV (E-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III | 
| Special features | reverse switching realizable | 
| Weight | approx. 55 g | 
| Operating temperature | -25…+55°C | 
| Storage temperature | -40…+85°C | 
| Relative humidity | 95%, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP20/variable | 
| Pluggable wiring | for all ESxxxx terminals | 
| Approvals/markings | CE, UL, DNV | 
| Housing data | EL-12-8pin | ES-12-8pin | 
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level | 
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm²,  st*: 0.08…2.5 mm², f*: 0.14…1.5 mm²  | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm²  | 
| Connection cross-section AWG | s*: AWG28…14,  st*: AWG28…14, f*: AWG26…16  | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16  | 
| Stripping length | 8…9 mm | 9…10 mm | 
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL2652 | EtherCAT Terminal, 2-channel relay output, 230 V AC, 300 V DC, 1 A | 
| ES2652 | EtherCAT Terminal, 2-channel relay output, 230 V AC, 300 V DC, 1 A, plug-in wiring level | 