The EL3312 analog input terminal allows thermocouples to be connected directly. The EtherCAT Terminal's circuit can operate thermocouple sensors using the 2-wire technique. Linearization over the full temperature range is realized with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3312 can also be used for mV measurement.
Product status:
regular delivery
Product information
| Technical data | EL3312 | 
|---|---|
| Number of inputs | 2 | 
| Power supply | via the E-bus | 
| Distributed clocks | – | 
| Input filter limit frequency | typ. 1 kHz | 
| Connection method | 2-wire | 
| Conversion time | approx. 1.2 s up to 20 ms, depending on configuration and filter setting, default: approx. 125 ms | 
| Voltage measurement | ±30/±60/±75 mV | 
| Resolution | 16 bit, representation adjustable: 0.1/0.01°C or 1/2/4 µV per digit | 
| Temperature measurement (thermocouple) | type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) | 
| Measurement uncertainty (temperature measurement) | at 23°C ambient temperature, with internal cold junction, according type:  B: ±8.5°C; C: ±6.2°C; E: ±2.5°C; J: ±2.7°C; K: ±3°C; L: ±2.3°C; N: ±3°C; R: ±6.7°C; S: ±7.1°C; T: ±2.9°C; U: ±2.5°C; for further details see documentation  | 
| Measurement uncertainty (voltage measurement) | at ±75 mV, 23°C ambient temperature: < ±0.14% (relative to full scale value) | 
| Electrical isolation | 500 V (E-bus/signal voltage) | 
| Current consumption E-bus | 200 mA | 
| Current consumption power contacts | – | 
| Special features | channel by channel wire break detection, internal and external cold junction, firmware filter adjustable | 
| Weight | approx. 60 g | 
| Operating temperature | -25…+60°C | 
| Storage temperature | -40…+85°C | 
| Relative humidity | 95%, no condensation | 
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. rating/installation pos. | IP20/variable | 
| Approvals/markings | CE, CCC, UL, ATEX, IECEx | 
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc  | 
| Housing data | EL-12-8pin | 
|---|---|
| Design form | compact terminal housing with signal LEDs | 
| Material | polycarbonate | 
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | 
| Side by side mounting by means of | double slot and key connection | 
| Marking | labeling of the BZxxxx series | 
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | 
| Connection cross-section | s*: 0.08…2.5 mm²,  st*: 0.08…2.5 mm², f*: 0.14…1.5 mm²  | 
| Connection cross-section AWG | s*: AWG28…14,  st*: AWG28…14, f*: AWG26…16  | 
| Stripping length | 8…9 mm | 
| Current load power contacts | Imax: 10 A | 
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | 
*s: solid wire; st: stranded wire; f: with ferrule