The EL1008 digital input terminal acquires the binary 24 V control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. Each EtherCAT Terminal has eight channels that indicate their signal state via light emitting diodes.
Special features:
- input specification type 1/3
- no bouncing due to mechanical switches thanks to 3 ms input filter
Product status:
regular delivery
Product information
| Technical data | EL1008 |
|---|---|
| Connection technology | 1-wire |
| Specification | EN 61131-2, type 1/3 |
| Number of inputs | 8 |
| Nominal voltage | 24 V DC (-15%/+20%) |
| “0” signal voltage | -3…+5 V (EN 61131-2, type 3) |
| “1” signal voltage | 11…30 V (EN 61131-2, type 3) |
| Input current | typ. 3 mA (EN 61131-2, type 3) |
| Input filter | typ. 3.0 ms |
| Distributed clocks | – |
| Current consumption power contacts | typ. 2 mA + load |
| Current consumption E-bus | typ. 90 mA |
| Electrical isolation | 500 V (E-bus/field potential) |
| Configuration | no address or configuration setting |
| Special features | standard input terminal for bouncing signals (filter 3 ms) |
| Weight | approx. 55 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/see documentation |
| Pluggable wiring | for all ESxxxx terminals |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV, cFMus |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Housing data | EL-12-8pin | ES-12-8pin |
|---|---|---|
| Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
| Material | polycarbonate | |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
| Side by side mounting by means of | double slot and key connection | |
| Marking | labeling of the BZxxxx series | |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
| Stripping length | 8…9 mm | 9…10 mm |
| Current load power contacts | Imax: 10 A | |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
*s: solid wire; st: stranded wire; f: with ferrule
| Ordering information | |
|---|---|
| EL1008 | EtherCAT Terminal, 8-channel digital input, 24 V DC, 3 ms |
| ES1008 | EtherCAT Terminal, 8-channel digital input, 24 V DC, 3 ms, plug-in wiring level |