The KL1808 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains eight channels, consisting of a signal input and 24 V DC, whose signal states are displayed by light emitting diodes. The power contacts are connected through. With the KL1808, the reference ground for all inputs is the 0 V DC power contact.
Special features:
- input specification type 1/3
- no bouncing due to mechanical switches thanks to 3 ms input filter
- tool-free connection by direct plug-in technology for solid wire conductors
- increased packing density with 16 connection points in the housing of a 12 mm terminal block
Product status:
regular delivery
Product information
Technical data | KL1808 |
---|---|
Connection technology | 2-wire |
Specification | EN 61131-2, type 1/3 |
Number of inputs | 8 |
Nominal voltage | 24 V DC (-15%/+20%) |
“0” signal voltage | -3…+5 V (EN 61131-2, type 1/3) |
“1” signal voltage | 11…30 V (EN 61131-2, type 3) |
Input filter | typ. 3.0 ms |
Input current | typ. 3 mA (EN 61131-2, type 3) |
Current consumption K-bus | typ. 15 mA |
Current consumption power contacts | typ. 2 mA + load |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | 8 inputs |
Configuration | no address or configuration setting |
Weight | approx. 60 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable (see documentation) |
Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | HD housing |
---|---|
Design form | HD (High Density) housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
Stripping length | 8…9 mm |
*s: solid wire; st: stranded wire; f: with ferrule