The KM2614 terminal module combines four pluggable power relays in one fieldbus module. The high switching capacity of 16 A at 230 V AC enables direct mains connection of consumers with high current consumption. The relays are positioned at the top and can therefore be exchanged easily. The KM2614 terminal module enables each relay to be manually switched to the ON status. A seal indicates the initial manual operation.
Product status:
regular delivery
Product information
Technical data | KM2614 |
---|---|
Number of outputs | 4 x change-over |
Nominal voltage | 230 V AC (max. switching voltage 250 V AC/30 V DC) |
Nominal switching current | 16 A |
Load type | ohmic, inductive, lamp load |
Max. output current | 16 A |
Operation | automatic operation/manual operation at the relay |
Switching current | 16 A AC/12 A DC at 30 V DC |
Minimum permitted load | 5 mA at 10 V |
Lamp test, electronic ballast | max. 25 A starting current |
Electrical isolation | 1.5 kV (K-bus/field potential); 2.5 kV rated surge voltage, overvoltage category III |
Current consumption power contacts | – |
Current consumption K-bus | typ. 15 mA |
Current consumption 24 V DC | 50 mA for each active relay |
Bit width in the process image | 4 outputs |
Operating cycles mech. (min.) | 5 x 106 |
Operating cycles electr. (min.) | 1 x 106 (1 A/250 V AC) |
Configuration | no address or configuration setting |
Special features | automatic/manual operation at the relay |
Dimensions (W x H x D) | 99 mm x 100 mm x 62 mm |
Weight | approx. 250 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE |