The analog KM4602 output terminal has two potential-free analog 0 to 10 V outputs. Both are connected internally to common ground. For each channel a switch enables selection between automatic or manual mode. In automatic mode an analog value is issued depending on the process data. With the manual switch settings the value set via the potentiometer is applied to the output. For manual mode a 24 V supply is required for the Bus Coupler. The switch state can be read by the controller.
Product status:
regular delivery
Product information
Technical data | KM4602 |
---|---|
Technology | single-ended |
Number of outputs | 2 |
Power supply | via the K-bus |
Signal voltage | 0…10 V |
Load | > 5 kΩ (short-circuit proof) |
Output error | < ±0.1% (relative to end value) |
Resolution | 12 bit |
Conversion time | ~ 1.5 ms |
Electrical isolation | 500 V (K-bus/signal voltage) |
Current consumption power contacts | – (no power contacts) |
Current consumption K-bus | typ. 175 mA |
Configuration | no address or configuration setting |
Special features | manual/automatic operation |
Weight | approx. 85 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE |
Housing data | KL-24 |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 24 mm x 100 mm x 52 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | – |
Wiring | specific push-in connection |