The EPI1809-0022 IO-Link box with digital inputs acquires the binary control signals from the process level and transmits them, in an electrically isolated form, to the controller. The state of the signals is indicated by light emitting diodes. The signals are connected via M12 screw type connectors.
Product status:
regular delivery
Product information
Technical data | EPI1809-0022 |
---|---|
Communication | IO-Link |
Interfaces | 1 x M12 plug, A-coded |
Data transfer rates | 230.4 kbaud (COM 3) |
Specification version | IO-Link V1.1, Class A |
Number of inputs | 16 |
Input connections | M12, screw type |
Nominal input voltage | 24 V DC (-15%/+20%) |
Input filter | 3.0 ms (default), adjustable 0…20 ms |
“0” signal voltage | -3…+5 V (EN 61131-2, type 3) |
“1” signal voltage | 11…30 V (EN 61131-2, type 3) |
Input current | typ. 3 mA (EN 61131-2, type 3) |
Sensor supply | max. 0.5 A, from L+, short-circuit proof in total |
Current consumption | typ. 100 mA from L+ |
Weight | approx. 250 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |
Housing data | 16 x M8, 8 x M12 |
---|---|
Dimensions (W x H x D) | 60 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3; 2 fixing holes 4.5 mm diameter for M4 |
Loading content ...
Loading content ...
Loading content ...
Loading content ...
© Beckhoff Automation 2024 - Terms of Use