The EL2252 digital output terminal connects the binary control output signals at the process level with electrical isolation. The outputs are switched precisely synchronised with the transferred time stamp, which has a resolution of 10 ns. This technology enables output switching times to be specified precisely across the system. The distributed clocks are used for reference. In conjunction with the EL1252 (digital input terminal with time stamp), the EL2252 enables responses with equidistant time intervals, largely independent of the bus cycle time. Each output can be switched to high resistance individually.
| Technical data | EL2252 | ES2252 |
|---|---|
| Number of outputs | 2 |
| Rated load voltage | 24 V DC (-15 %/+20 %) |
| Load type | ohmic, inductive, lamp load |
| Resolution time stamp | 1 ns |
| Precision of time stamp in the terminal | 10 ns (+ output circuit drift) |
| Distributed clock precision | << 1 µs |
| Output delay through 24 V power section | typ. < 1 µs |
| Max. output current | 0.5 A (short-circuit-proof) per channel |
| Current limitation | typ. 1.5 A |
| Breaking energy | < 150 mJ/channel |
| Switching times | see documentation |
| Current consumption E-bus | typ. 130 mA |
| Electrical isolation | 500 Vrms (E-bus/field potential) |
| Current consumption power contacts | typ. 15 mA + load |
| Bit width in the process image | 8 bit output (ch. 1 + ch. 2), 9 byte time stamp |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all ESxxxx terminals |