Communication
EL6692
 
EtherCAT bridge terminal EL6692
Status LEDs
EtherCAT
input
EtherCAT
output
24 V
Top view

EL6692 | EtherCAT bridge terminal

The EtherCAT bridge terminal EL6692 enables data exchange between EtherCAT strands with different masters. It also enables synchronisation of the distributed clocks of the individual strands. The power supply on the primary side (E-bus) comes from the E-bus, on the secondary side (RJ 45) via an external connection. If several EL6692 are used, data traffic to the terminals on the other side can continue in the event of a power supply failure on one side.

Technical data EL6692
Ports primary: E-bus, secondary: 2 x RJ 45 EtherCAT input/output
Cable length 100 m 100BASE-TX, secondary port
Hardware diagnosis status LEDs
Power supply primary: via the E-bus, secondary: via connector
Electrical isolation 500 Vrms (E-bus/secondary side)
Current consumption E-bus: 120 mA; external: 60 mA/24 V (see documentation)
Bit width in the process image 16 bit SYNC input + IO input/output
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable