Analog Output
KL4112
+ Output 1
Shield
Power contact 0 V
Power contact
+24 V
+ Output 2
+24 V
0 V
Shield
Run LED1
Run LED2
Top view
Contact assembly
Connection
KL4112 | 2-channel analog output terminal 0…20 mA
The KL4112 analog output terminal generates analog output signals in the range from 0 to 20 mA. The power is supplied to the process level with a resolution of 16 bits (default: 15 bits), and is electrically isolated. Ground potential for the output channels of a Bus Terminal is common with the 24 V DC supply. The output stages are powered by the 24 V supply. The two run LEDs give an indication of the data exchange with the Bus Coupler.
| Technical data |
KL4112 | KS4112 |
| Number of outputs |
2 |
| Power supply |
24 V DC via the power contacts (alternative 15 V DC with Bus Terminal KL9515) |
| Signal current |
0…20 mA |
| Load |
< 500 Ω |
| Measuring error |
< ±0.1 % (relative to full scale value) |
| Resolution |
15 bit, configurable to 16 bit |
| Conversion time |
~ 3.5 ms |
| Electrical isolation |
500 Vrms (K-bus/signal voltage) |
| Current consumption K-bus |
typ. 60 mA |
| Bit width in the process image |
output: 2 x 16 bit data (2 x 8 bit control/status optional) |
| Configuration |
no address or configuration setting |
| Weight |
approx. 80 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |
| Pluggable wiring |
for all KSxxxx Bus Terminals |
| Special terminals |
|
| KL4112-0010 |
Siemens S5 format |
| KL4112-0050 |
Siemens S7 format |