PROFIBUS
BK3150
Fieldbus connection
Address selector
Configuration interface
Status display fieldbus,
power LEDs
Bus Coupler
supply
K-bus
Input for
power contacts
Power contacts
BK3150 | PROFIBUS DP “Compact” Bus Coupler
The “Compact” Bus Coupler BK3150 for PROFIBUS DP extends the Beckhoff Bus Terminal system by a cost-optimised version in a compact housing. Up to 64 Bus Terminals are supported; with the terminal bus extension, up to 255 Bus Terminals can be connected. The PROFIBUS Bus Coupler offers automatic baud rate detection up to 12 Mbaud and two address selection switches for address assignment. For the fieldbus connection, a D-sub 9-pin socket for the ZS1031-3000 or ZB3100 PROFIBUS connectors is available.
| System data |
PROFIBUS | BK3150 |
| Number of I/O stations |
100 with repeater |
| Number of I/O points |
approx. 6,000, depending on the master |
| Data transfer medium |
shielded copper cable, 2 x 0.25 mm² |
| Max. cable length |
| 1,200 m |
1,000 m |
400 m |
200 m |
100 m |
|
| Data transfer rates |
9.6/19.2/ 93.75 kbaud |
187.5 kbaud |
500 kbaud |
1,500 kbaud |
…3, 6, 12 Mbaud |
|
| Data transfer time |
| approx. 3 ms (10 stations for 32 bit input and output each) |
|
|
approx. 0.5 ms |
|
|
| Technical data |
BK3150 |
| Number of Bus Terminals |
64 (255 with K-bus extension) |
| Max. number of bytes fieldbus |
128 byte input und 128 byte output |
| Data transfer rates |
automatic detection up to 12 Mbaud |
| Bus interface |
1 x D-sub 9-pin socket with shielding |
| Power supply |
24 V DC (-15 %/+20 %) |
| Input current |
70 mA + (total K-bus current)/4, 500 mA max. |
| Supply current K-bus |
1,000 mA |
| Power contacts |
24 V DC max./10 A max. |
| Electrical isolation |
500 Vrms (power contact/supply voltage/fieldbus) |
| Weight |
approx. 100 g |
| Operating/storage temperature |
0…+55 °C/-25…+85 °C |
| Relative humidity |
95 %, no condensation |
| Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. |
IP 20/variable |