The KL2761 dimmer Bus Terminal is intended for direct connection of different lighting devices. Typical lighting devices such as incandescent lamps, inductive and electronic ballasts are detected and controlled in the right mode. The required light intensity values are specified via the process data. The KL2761 calculates the correct phase control angle for the required value. The output is short-circuit-proof and overload-proof. The KL2761 can be operated at any fieldbus. The load status can be read.
| Technical data | KL2761 | KS2761 |
|---|---|
| Mains voltage | 230 V AC |
| Rated output | 600 VA (W) |
| Rated current | max. 2.7 A |
| Load type | ohmic, inductive or capacitive (not mixed), automatic load detection |
| Control type | phase control |
| Resolution | 1 % |
| Electrical isolation | 500 Vrms (K-bus/field voltage), 3,750 V AC (1 min.) |
| Leakage current | < 1 mA (OFF state) |
| Current consumption K-bus | typ. 65 mA |
| Bit width in the process image | output: 1 x 16 bit data (1 x 8 bit control/status optional) |
| Weight | approx. 60 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
Product announcement |
KL2761: available KS2761: estimated market release 1st quarter 2009 |