Special Function
KL6401
 
LON Bus Terminal KL6401
Service
+ 24 V
0 V
LON+
Service
+ 24 V
0 V
LON-
Run
Error 1
LON service/status
Error 2
LON ICOM
Top view
Contact assembly
Service
Service
Power contact 0 V
Power contact
+24 V

KL6401 | LON Bus Terminal

The KL6401 LON Bus Terminal enables direct connection of LON devices. The network variables of the connected devices are available for the Bus Coupler or the higher-level bus system. This simplifies the data exchange between a variety of systems and a LON network. Status LEDs directly indicate the bus status. The LON terminal operates independent of the bus system used. Several KL6401 can be used with a single Bus Coupler or a Bus Terminal Controller. The KL6401 supports 62 SNVTs. All SNVT types can be configured as input or output variable via the KS2000 software. The KS2000 software generates an XIF file that is integrated in an LON tool.

Technical data KL6401 | KS6401
Data transfer channels 1
Network variables 62 (standard network variables SNVTs), max. 15 LON devices
Data transfer standard FTT-10, LPT
Data transfer rates 78 kbit/s
Bus segment length 500 m
Current consumption K-bus approx. 55 mA
Electrical isolation 500 Vrms (K-bus/LON-bus)
Bit width in the process image input/output: 36 bytes
Configuration KS2000, LonMaker or another LON Tool, TwinCAT (function blocks)
Weight approx. 85 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27/29
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Product announcement
KL6401: available
KS6401: estimated market release 4th quarter 2008