The digital KM2642 output terminal has two independent relay change-over contacts, which can be used for switching mains current consumers. For each channel a switch enables selection between automatic, manual on, manual off. In automatic mode the logical state of an output bit switches the relay. For manual mode a 24 V supply is required for the Bus Coupler. The output state can be read by the controller.
| Technical data | KM2642 |
|---|---|
| Number of outputs | 2 x change-over |
| Switching capacity max. | 3 kVA |
| Switching voltage max. | 250 V AC |
| Switching current max. | 6 A AC |
| Current consumption K-bus | typ. 130 mA |
| Contact material | AgSnO2 |
| Bit width in the process image | 2 inputs (status manual, automatic), 2 outputs |
| Operating cycles | 106 |
| Configuration | no address or configuration setting |
| Weight | 110 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
Product announcement |
estimated market release 3rd quarter 2008 |