The EK1000 coupler connects EtherCAT with the EtherCAT Terminals (ELxxxx). One station consists of an EK1000 coupler, any number of EtherCAT Terminals and a bus end terminal. The Coupler converts the passing telegrams from Ethernet 100BASE-TX to E-bus signal representation. Additionally, it is able to process the EtherCAT UDP protocol in passing. The Coupler is connected to the network via the upper Ethernet interface. The lower RJ 45 socket may be used to connect further EtherCAT devices in the same strand. In the EtherCAT network, the EK1000 coupler is installed directly at the switch. The couplers EK1100 (for E-bus components) or BK1120 (for K-bus components) are suitable for installation at other locations within the Ethernet signal transfer (100BASE-TX).
| Technical data | EK1000 |
|---|---|
| Task within EtherCAT system | coupling of EtherCAT Terminals (ELxxxx, except fieldbus terminals) to 100BASE-TX Ethernet networks; operation at the switch |
| Number of EtherCAT Terminals | up to 65,535 |
| Type/number of peripheral signals | unlimited |
| Data transfer medium | Ethernet/EtherCAT CAT5 cable |
| Distance between stations | 100 m (100BASE-TX) |
| Protocol | EtherCAT, EtherCAT UDP |
| Delay | approx. 1 µs |
| Data transfer rates | 100 Mbaud |
| Configuration possibility | KS2000 software or via EtherCAT (ADS) |
| Bus interface | 2 x RJ 45 |
| Power supply | 24 V DC (-15 %/+20 %) |
| Input current | 70 mA + (total E-bus current)/4 |
| Current consumption E-bus | up to 2 A |
| Power contacts | 24 V DC max./10 A max. |
| Electrical isolation | 500 Vrms (power contact/supply voltage/Ethernet) |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 20/variable |
Product announcement |