The IP4112 analog output module generates analog output signals in the range from 0/4 to 20 mA. The power is supplied to the process level with a resolution of 15 bits (default), and is electrically isolated. If the input is transmitted without an arithmetical sign, 16 bit resolution may also be selected. If necessary, the output scaling can be altered.
Ground potential for the four output channels is common with the 24 V DC supply. The output drivers are powered by the load voltage. The applied auxiliary voltage (which can be any value up to 30 V DC) is fed through to supply the actuators.
| Technical data | IP4112-Bxxx |
|---|---|
| Number of outputs | 4 |
| Output connections | M12, screw type |
| Signal current | 0/4…20 mA |
| Load | < 500 Ω |
| Resolution | 15 bit, configurable to 16 bit |
| Conversion time | < 4 ms |
| Measuring error | < ±0.1 % (relative to full scale value) |
| Actuator supply | from the auxiliary voltage UP |
| Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
| Bit width in the process image | output: 4 x 16 bit data, optional: 4 x 8 bit control/status |
| Electrical isolation | channels/control voltage: yes, between the channels: no, control voltage/fieldbus: depends on the bus system |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |