The EPP1322-0001 EtherCAT P junction in IP67 are available for flexible topology configurations. The current carrying capacity of 3 A per EtherCAT P segment for US and UP already enables a wide range of sensors and actuators to be used. For larger or more branched machines/systems a power supply boost may be required. The EPP1332-0001 EtherCAT P junction with refresh feature can be used for feeding in US or UP at any point in the system.
The EPP1342-0001 should be used for topological branches without the need for voltage boosting. All infrastructure box modules feature status LEDs for EtherCAT, US and UP.
Product status:
regular delivery
Product information
Technical data | EPP1322-0001 |
---|---|
Protocol | EtherCAT/EtherCAT P |
Bus interface | 1 x M8 socket, shielded, 1 x M8 socket, P-coded, shielded |
Task within EtherCAT system | coupling to the EtherCAT network, EtherCAT P junction and feed-in of US and UP |
Number of channels | IN: 1 x EtherCAT, OUT: 3 x EtherCAT P |
Nominal voltage | 24 V DC (-15%/+20%) |
Total current | max. 3 A per US and UP for all EtherCAT P ports in total |
Current consumption from US | typ. 100 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
Distributed clocks | – |
Distance between stations | 100 m (100BASE-TX) |
Data transfer rates | 100 Mbit/s |
Configuration | not required |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |
Housing data | 8 x M8, 4 x M12 |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |