The EL2819 digital output terminal connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. The EtherCAT Terminal has 16 channels, whose signal states are indicated by LEDs. The integrated diagnostics can be evaluated in the controller and is indicated by the LEDs. Maintenance of the application is simplified by the diagnostics. The power contacts are connected through. The reference ground for the outputs is the 0 V DC power contact. The outputs are electrically isolated from the fieldbus side.
Special features:
- Connection of different load types possible (ohmic, inductive, lamp load)
- Max. output current 0.5 A per channel
- Short-circuit-proof outputs and reverse polarity protection
- Integrated diagnostics option, including
- Short-circuit detection per channel
- Wire breakage per channel
- Overcurrent per channel
- Overtemperature
- Voltage loss and undervoltage
- Parameterizable output behavior in case of bus error (safe state)
- Tool-free connection by direct plug-in technology for solid wire conductors
Product status:
regular delivery
Product information
Technical data | EL2819 |
---|---|
Connection technology | 1-wire |
Number of outputs | 16 |
Nominal voltage | 24 V DC (-15%/+20%) |
Load type | ohmic, inductive, lamp load |
Distributed clocks | – |
Max. output current | 0.5 A (short-circuit proof) per channel |
Output stage | push (high-side switch) |
Short-circuit current | typ. < 1 A |
Reverse voltage protection | yes |
Breaking energy | < 150 mJ/channel |
Current consumption E-bus | typ. 90 mA |
Electrical isolation | 500 V (E-bus/field potential) |
Current consumption power contacts | typ. 50 mA + load |
Bit width in the process image | 16 bit output and diagnostics |
Special features | diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel) |
Weight | approx. 70 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/see documentation |
Approvals/markings | CE, UL, ATEX, IECEx, DNV GL |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | EL-12-16pin |
---|---|
Design form | HD (High Density) housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule