The EP6224-3002 IO-Link module enables the connection of up to four IO-Link devices. These can be actuators, sensors or a combination of both. An additional supply voltage is available on the Class B ports for IO-Link devices with higher power requirements. A point-to-point connection is used between the box and the device. The EtherCAT Box is parameterized via the EtherCAT master. IO-Link is designed as an intelligent link between the fieldbus levels and the sensor, wherein parameterization information can be exchanged bidirectionally via the IO-Link connection. The parameterization of the IO-Link devices with service data can take place from TwinCAT via ADS or, very conveniently, via the integrated IO-Link configuration tool.
In the standard setting, the EP6224-3022 functions as a 4-channel input module, 24 V DC, which communicates with connected IO-Link devices, parameterizes them and, if necessary, changes their operation mode. Each IO-Link port can also be used optionally as a pure input or output. The slim design also enables use in confined spaces.
Special properties:
- IO-Link V1.1
- convenient sensor parameterization in TwinCAT
- additional supply P24
- very slim design
Product status:
regular delivery
Product information
Technical data | EP6224-3002 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, 4-pin, a-coded, shielded |
Data transfer rates | 4.8 kbaud, 38.4 kbaud and 230.4 kbaud |
Connection method | M12 socket, 5-pin, a-coded |
Specification version | IO-Link V1.1, Class B |
IO-Link interfaces | 4 |
Nominal voltage | 24 V DC (-15%/+20%) |
Distributed clocks | yes |
IO-Link sensor supply L+ | 24 V DC, 1.4 A per port, ∑ 4.0 A for 4 ports |
IO-Link extra power P24 | 24 V DC, 2.0 A per port, ∑ 4.0 A for 4 ports |
Current consumption from US | typ. 100 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
Electrical isolation | 500 V |
Special features | IO-Link master, Class B, in slim housing |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60°C/-40…+85°C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Approvals/markings | CE, UL |
Housing data | 8 x M8, 4 x M12 |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |