The EL1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
Product status:
regular delivery
Product information
Technical data | EL1054 |
---|---|
Technology | NAMUR |
Connection technology | 2-wire |
Specification | NAMUR DC switching amplifier (IEC 60947-5-6) |
Signal type | binary, current input for NAMUR sensors |
Number of inputs | 4 |
Open circuit voltage | typ. 8.2 V DC |
“0” signal current | ≤ 1.2 mA |
“1” signal current | ≥ 2.1 mA |
Switching hysteresis | typ. 350 µA |
Short-circuit current | typ. 7.8 mA |
Fault detection | I ≤ 200 µA (cable break), I ≥ 7.0 mA (short circuit) |
Max. switching frequency | 5 kHz (duty factor 50 %) |
Internal resistance | according to I/V curve IEC 60947-5-6 |
Distributed clocks | – |
Supply voltage electronics | 24 V DC (via power contacts) |
Current consumption E-bus | typ. 50 mA |
Electrical isolation | 500 V (E-bus/field potential) |
Special features | integrated reverse polarity protection |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
Housing data | EL-12-8pin | ES-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 | s*: AWG28…16, st*: AWG28…16, f*: AWG26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Ordering information | |
---|---|
EL1054 | EtherCAT Terminal, 4-channel digital input, NAMUR |
ES1054 | EtherCAT Terminal, 4-channel digital input, NAMUR, pluggable wiring |